The BDM800 Beam Detector Module is designed to interface the MZX FireRay3000/5000 Beam Detectors to the MZX Digital Addressable Loop. The BDM800 provides power from the loop, monitors the Fire and Fault Relay Contacts of the detector and also monitors the wiring to the detector for open and short circuit faults.
The BDM800 can be used to power the complete MZX FireRay 2000 system (via the loop) or just the control and receiver units with a second BDM800 used to power the transmitter unit. Up to fourteen BDM800’s driving MZX FireRay 3000/5000 reflective beam detectors can be connected to a single loop.
Features:
- Powers Beam Detectors directly from the MZX Digital Loop
- Reduces wiring and installation costs
- Monitors Beam Detectors for Fire and Fault
- Monitors interconnections for open and short circuit faults
- LPCB and VdS Approved
- Can be installed to BS5839 Part 1:2002
- Onboard LED indicates polling and activation
- Compatible with the MZX FireRay 3000/5000 beam detector
- Optional BTM800 beam termination module to further simplify installation
- Supplied fitted to a standard double gang ancillary front cover